All Categories
History
Response Rate
100.0%
Response Time
37.6hours
Product
Thyristor type power regulator Three-phase power regulator PAC46 seriesHandling Company
SHIMADENCategories
Image | Part Number | Price (excluding tax) | Power supply voltage | Current capacity | Current limit function (optional) | Applicable load | Output limit function at startup | Mass () is with heatsink | Alarm output | Withstand voltage | Insulation resistance | External output adjustment function (optional) | Control output range | Control input | Output current detection | Cooling method | Protection function | Operating temperature range | Feedback function (phase control) | Soft start function |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
PAC46 |
Available upon quote |
200V, 220V, 240V, 380V, 400V, 440V AC 50/60Hz |
20A, 30A, 50A, 75A, 100A, 150A, 200A, 300A, 500A, 600A |
Output 0~60%/1~60 seconds limit |
Resistive load, inductive load |
Output 0~60%/1~60 seconds limit |
20A, 30A: Approx. 5kg 50A, 75A, 100A: Approx. 6kg 150A, 200A, 300A: Approx. 15kg 500A, 600A: Approx. 42kg |
1 point 1C contact 240V AC 1A Isolated from the system Overcurrent, internal temperature abnormality, fuse blown |
Between power terminal and ground terminal 200-240V: 2000V AC for 1 minute 380-440V: 2500V AC for 1 minute |
Between power supply terminal and ground terminal 500V DC 20MΩ or more |
By connecting an external regulator (sold separately) |
0~98% or more |
4~20mA, 0~10V, 1~5V DC |
By built-in CT |
20A, 30A: Natural cooling type, 50A~600A: Forced air cooling type |
Overcurrent detection (stops at 110% of constant current), fast-acting fuse |
-10~50℃ (Reduction of current is required above 40℃.) |
Constant voltage, constant current, constant power, voltage squared |
Approximately 1~30 seconds |