All Categories
History
Response Rate
100.0%
Response Time
37.6hours
Product
Thyristor type power regulator Single phase power regulator PAC26 seriesHandling Company
SHIMADENCategories
Image | Part Number | Price (excluding tax) | Power supply voltage | Current capacity | Current limit function (optional) | Applicable load | Fast-blow fuse (optional) | Output limit function at startup | Mass () is with heatsink | Alarm output | Withstand voltage | Insulation resistance | External output adjustment function (optional) | Control output range | Control input | Output current detection | Cooling method | Protection function | Operating temperature range | Feedback function (phase control) | Soft start function |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
PAC26 |
Available upon quote |
100~110V, 110~120V, 200~220V, 220~240V |
20・30・45・60・80・100・150・250・350・450A |
50~100% |
Resistive load, inductive load |
Built-in |
0~60%, 1~60sec |
20/30A: Approx. 3.0kg, 45/60A: Approx. 3.8kg, 80/100A: Approx. 6.1kg |
1a 240V AC 1A system and insulation, overcurrent, fan, fuse, etc. |
100~240V between power terminal and ground terminal 2000V AC for 1 minute |
Between power supply terminal and ground terminal 500V DC 20MΩ or more |
By connecting an external regulator (sold separately) |
0~97% or more |
4~20mA, 0~10V, 1~5V DC, contact, etc. |
By built-in CT |
20~100A: Natural cooling type, 150~450A: Wind cooling type |
Overcurrent detection (stops at 130% of rated current), fast-acting fuse |
-10~50℃, 90%RH or less (no condensation) |
Constant voltage, constant current, constant power, power linear output |
1~10sec |
Reviews shown here are reviews of companies.
Reviews shown here are reviews of companies.