About This Product

Ethernet Multiprotocol Ethernet compatible remote I/O is a new remote I/O system proposed by TURCK. One remote I/O unit supports three types of industrial Ethernet communication. Remote I/O identifies the connected network protocol and automatically begins communication. Since it is compatible with PROFINET®️, EtherNet/IP™, and Modbus®️ TCP, it helps reduce design man-hours and the number of models for system vendors and machine manufacturers who have to change network protocols for each user.

■TBEN-S2 analog I/O terminal supports many analog signals. Signal type and input filter value can be set for each connection port.

・Automatically recognizes industrial Ethernet protocols, compatible communication protocols: PROFINET®️, EtherNet/IP™, Modbus®️ TCP ・Analog input/output type can be selected using the web server function ・Field logic controller function compatible (FLC) ・Supports open industrial interface standard FDT technology Network specifications

■Modbus®️ TCP

Support function code: FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23

■EtherNet/IP™

・Recommended cycle time: 10ms or more ・Quick Connect (QC) compatible 500ms or less ・Device Level Ring (DLR) compatible

■PROFINET®️

・Minimum cycle time: 1ms ・Supported functions: Fast Start-UP (FSU) 500ms or less, Automatic Addressing Media Redundancy Protocol (MRP), PROFINET alarm handling

  • Product

    IP67 compatible block type remote I/O compact remote I/O TBEN-S series analog I/O

Share this product


70+ people viewing

Last viewed: 37 minutes ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

1 Models of IP67 compatible block type remote I/O compact remote I/O TBEN-S series analog I/O

Image Part Number Price (excluding tax) Communication protocol Vibration resistance test/shock resistance test Temperature range Material Main unit power voltage Compatible input/output signals Size Resolution Output signal Input signal Protective structure Connector Ethernet communication specifications Analog output Analog input Web server Supply current to I/O EMC
IP67 compatible block type remote I/O compact remote I/O TBEN-S series analog I/O-Part Number-TBEN-S series analog I/O

TBEN-S series analog I/O

Available upon quote

PROFINET®️, EtherNet/IP™, Modbus®️ TCP automatic recognition supported

Vibration test EN 60068-2-6 20g, Shock test EN 60068-2-27, Drop test EN 60068-2-31/IEC 60068-2-32

Operating temperature range –40~+70 ℃, Storage temperature range –40~+85 ℃

Body resin part PA6-GF30, connector metal part stainless steel

DC 24V (Allowable voltage range DC 18~30V)

Analog voltage / analog current / thermocouple / resistance temperature detector / resistance

Length 145 x width 32 x height 32 mm

16 bit

Analog voltage: 0~10V, ±10V, 2~10V, 0~5V, 1~5V
Analog current: 0~20 mA, 4~20 mA

Analog voltage: 0~10 V, ±10 V, 2~10 V, 0~5 V, 1~5 V, ±1 V, ±500 mV, ±100 mV, ±50 mV
Analog current: 0~20 mA, 4~20 mA, ±20 mA

IP65, IP67, IP69K

Ethernet connector M8 4-pin A code x 2 ports
I/O connector M12 5 pin A code x 4 ports
Power connector M8 4 pin x 2 ports

10 Mbps/100 Mbps, Full/Half Duplex, auto negotiation, auto crossing, various settings possible

Power supply voltage: DC 24V (supplied from power supply V2) maximum 4A / 4ch total. Since the short circuit is not equipped, please use a circuit breaker such as a fuse on the power supply line to this machine.
Cycle time: 4ms

Power supply voltage: DC 24V (supplied from power supply V1), short circuit detection 1.0 A / 4 channels total
Cycle time: Analog current and analog voltage 4 ms. Temperature sensor and resistor 400 ms

Factory default 192.168.1.254 (subnet mask 255.255.255.0)

Isolation groups V1 and V2 both max. 4.0 A. However, the total of V1 and V2 is maximum 5.5 A.

EN 61131-2

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Ethernet Switches Products

Other products of NC Automation Co., Ltd.

Reviews shown here are reviews of companies.


View more products of NC Automation Co., Ltd.

About Company Handling This Product

Response Rate

100.0%


Response Time

18.5hrs


Company Review

5.0
  • Japan

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2024 Metoree