All Categories
History
Price (excluding tax)
■Debris load ・Impact test as a system test: 3 shocks of 200 kg from 1.5 m after heating for 45 minutes ・Impact test as a system test: 1 impact of 200 kg from 1.5 m after heating for 30 minutes ■Fire resistance performance ECB·S certification according to EN 1047-2, 50 K temperature rise and 85 % relative humidity up to 24 hours (additional heat period), 60 minutes flame exposure. ・As a F120 system test, the cell structure and its built-in modules are tested according to the limits of EN 1363 (DIN 4102). ■Water ・Static water, 72 hours, 40cm, max. 20 drops - Fire extinguishing water, IP x 6, system test according to EN 60529, on cell structure and its built-in modules - Relative humidity, 85%, >24 hours (additional heat period), 60 minutes flame exposure, according to EN 1047-2 ・Relative humidity 85%, 30 minutes or more
You can search for other models from each index. The displayed value is the value of the currently selected part number.
1 pack (pieces)
Corrosive combustion gas
Debris load
Dustproof performance
EMC protection
Fire resistance
Specification
Water
Part Number
RM7857.972Handling Company
Rittal GmbH & Co. KGImage | Price (excluding tax) | 1 pack (pieces) () | Corrosive combustion gas () | Dustproof performance () | EMC protection () | Specification () |
---|---|---|---|---|---|---|
![]() |
Available upon quote | 1 | Combustion gas protection according to DIN 18 095 | As a system test according to IP 5x EN 60 529 for cell structures and their integrated modules | Protection against radio frequency incidence and radiation, according to similar component tests by RWTH Aachen University | High effective space |