■Low wind pressure aluminum conductor cross-linked polyethylene insulated wire for 22/33kV This is a standard specification low wind pressure wire that has the maximum wind pressure reduction effect at Class A wind pressure (40m/s).
You can search for other models from each index. The displayed value is the value of the currently selected part number.
AC maximum conductor resistance (90℃) (Ω/km)
Approximate mass (kg/km)
Conductor composition Aluminum (pieces/shape)
Conductor composition Steel (pcs/mm)
Conductor continuous allowable temperature (℃)
Conductor outer diameter approx. (mm)
Continuous allowable current (A)
DC maximum conductor resistance (20℃) (Ω/km)
Finished outer diameter approx. (mm)
Insulator thickness approx. (mm)
Mechanical properties Conductor tensile load (kN)
Mechanical properties Elastic modulus (kN/mm2)
Mechanical properties Linear expansion coefficient (1/K)
Minimum insulation resistance (20℃) (MΩ・km)
Number of grooves (pieces), groove depth approx. (mm)
Reactance (900mm between equivalent lines) (Ω/km)
Wind pressure load 45m/s
Wind pressure load 50m/s
Wind pressure load Class A (40m/s) (Pa)
Wind pressure load Class C (28m/s) (Pa)
Withstand voltage (kV/1 minute)
Part Number
22/33kV RW-AL-OC (200㎟)Handling Company
Daiden Co., Ltd.Categories
Image | Price (excluding tax) | AC maximum conductor resistance (90℃) (Ω/km) | Approximate mass (kg/km) | Conductor composition Aluminum (pieces/shape) | Conductor continuous allowable temperature (℃) | Conductor outer diameter approx. (mm) | Continuous allowable current (A) | DC maximum conductor resistance (20℃) (Ω/km) | Finished outer diameter approx. (mm) | Insulator thickness approx. (mm) | Mechanical properties Conductor tensile load (kN) | Mechanical properties Elastic modulus (kN/mm2) | Mechanical properties Linear expansion coefficient (1/K) | Minimum insulation resistance (20℃) (MΩ・km) | Number of grooves (pieces), groove depth approx. (mm) | Reactance (900mm between equivalent lines) (Ω/km) | Wind pressure load 45m/s | Wind pressure load 50m/s | Wind pressure load Class A (40m/s) (Pa) | Wind pressure load Class C (28m/s) (Pa) | Withstand voltage (kV/1 minute) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
![]() |
Available upon quote | 0.193 | 785 | 19/SB | 90 | 17 | 455 | 0.15 | 24.6 | 3.8 | 26.28 | 61.8 | 230×10^-7 | 1,500 | 18,0.50 | 0.37 | 900 | 1,110 | 720 | 490 | Twenty five |
Reviews shown here are reviews of companies.
Reviews shown here are reviews of companies.
Response Rate
100.0%
Response Time
16.6hrs