All Categories
History
Price (excluding tax)
■Features ・Built-in pump/tank type ・Energy saving 50% ・50% reduction in CO2 emissions ・Precise temperature control possible ・Can be installed in close contact continuously ・Water-cooled type that does not emit waste heat into the room ■Applications Industrial Food Agricultural IC/Medical field
You can search for other models from each index. The displayed value is the value of the currently selected part number.
Accessories
COP (cooling capacity/power consumption)
Carbon dioxide equivalent value (tons)
Cold water amount (L/min)
Cold water tank actual capacity (L)
Compressor
Compressor rating (kw)
Condenser
Cooler
Cooling capacity (kw)
Cooling water control method
Current (A)
External dimensions (width x depth x height) (mm)
External signal
G.W.P.
Installation location
Liquid used
Operating ambient temperature range (℃)
Operating liquid temperature range (℃)
Operating sound dB (A)
Operation control method
Outlet temperature accuracy (℃)
Power consumption (kw)
Power supply
Product mass (dry mass) (kg)
Protection device
Pump
Refrigerant control method
Refrigerant filling amount (g)
Refrigerant type
Part Number
MC4830VBW1-PTHandling Company
Meiwa Co., Ltd.Categories
Image | Price (excluding tax) | Accessories | COP (cooling capacity/power consumption) | Carbon dioxide equivalent value (tons) | Cold water amount (L/min) | Cold water tank actual capacity (L) | Compressor | Compressor rating (kw) | Condenser | Cooler | Cooling capacity (kw) | Cooling water control method | Current (A) | External dimensions (width x depth x height) (mm) | External signal | G.W.P. | Installation location | Liquid used | Operating ambient temperature range (℃) | Operating liquid temperature range (℃) | Operating sound dB (A) | Operation control method | Outlet temperature accuracy (℃) | Power consumption (kw) | Power supply | Product mass (dry mass) (kg) | Protection device | Pump | Refrigerant control method | Refrigerant filling amount (g) | Refrigerant type |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
![]() |
Available upon quote | ・Y-type strainer (80 mesh) ・Nipple 3/4B | 2.2/2.09 | 2.5 | 26 (lifting height 15/21m) | 15 | Fully enclosed rotary type (DC inverter drive) | 2.25 | Water-cooled double pipe type | Plate type (SUS316 copper brazing) | 4.8 | Water control valve | 10.4/10.9 | 500×795×910 | Input: No-voltage contact input (operation) Output: No-voltage contact output (operation/abnormality) | 2,090 | Indoor floor-standing | Brine (Knight Brine Z1) | 2~43 | -10~10 | 48/48 | Compressor rotation speed control | ±0.1 (when load, ambient temperature, and power supply are stable) | 2.18/2.29 | 3 phase 200V±10% 50/60Hz | 110 | High pressure switches, freeze sensors, overcurrent relays, high and low pressure sensors, water level switches, winding protection thermos | Stainless steel immersion multistage pump | Linear expansion valve | 1,200 | R410A |
Reviews shown here are reviews of companies.
Reviews shown here are reviews of companies.
Response Rate
100.0%
Response Time
49.2hrs
Company Review
4.0