HVAC Industry / BAS CO2 concentration monitoring (CO2) Transmitter -CDT2000-CDT2000
HVAC Industry / BAS CO2 concentration monitoring (CO2) Transmitter -CDT2000-Krone Co., Ltd.

HVAC Industry / BAS CO2 concentration monitoring (CO2) Transmitter -CDT2000
Krone Co., Ltd.


About This Product

■ Characteristics ・ The CDT2000 series can measure CO2 concentration and temperature (humidity), and is designed to be used in HVAC/R industry, office, public space, conference room, and classroom. -The terminal is equipped with a large and easy -to -read touch screen liquid crystal, can easily set up various settings, and is equipped with automatic school regular * 1. ・ The CDT2000-DC is a dual channel model equipped with a measurement channel and a reference channel, can be continuously compared and adjusted. * 1 Automatic proofreading is valid in a ventilation situation for about 4 hours a day so that the CO2 concentration decreases to the outdoor level. ■ Application example ・ Office, hospital, public space, conference room, classroom CO2 concentration and humidity measurement ・ Supply in the ventilation system and CO2 concentration / humidity measurement in exhaust system ・ Environmental monitoring in HVAC/R environment ・ Stable CO2 supply monitoring in plastic

  • Product

    HVAC Industry / BAS CO2 concentration monitoring (CO2) Transmitter -CDT2000

Share this product


160+ people viewing


Free
Since our quotes are free, feel free to use our service.

No Phone Number Required
You won’t have to worry about receiving unnecessary calls.

1 Models of HVAC Industry / BAS CO2 concentration monitoring (CO2) Transmitter -CDT2000

Product Image Part Number Price (excluding tax) Accuracy CO₂ Accuracy relative humidity (optional) Accuracy temperature Display (optional) Input power supply Material Measurement medium Measurement range CO₂ Measurement range relative humidity (optional) Measurement range temperature Measurement unit Measuring element Mounting Operating environment Output signal CO₂ Output signal relative humidity (optional) Output signal temperature Proofreading Protection grade Relay output (optional) Standards / authentication Wiring connection power supply supply Wiring connection relay output power consumption size weight
HVAC Industry / BAS CO2 concentration monitoring (CO2) Transmitter -CDT2000-Part Number-CDT2000

CDT2000

Available upon quote ± 40ppm+2 % RD
* DC model: ± 75ppm or 10 % RD
± 2… 3 % RH (0… 50 ° C/10… 90 % RH)
* TEB (Total Error Band): 5… 50 ° C/10… Includes accuracy, hysteresis, and temperature effects when it exceeds 90 % RH
<0.5 ℃ 3 1/2 digits LCD (touch screen) 24VAC or 24VDC, ± 10 % Case: ABS Dry air or non -corrosion gas 400 ... 2,000ppm 0… 100 % 0… 50 ℃ PPM, ℃, % RH CO₂: Unpaptured infrared (NDIR)
Temperature: PT1000
Relative humidity (option): thermal hardening polymer electrostatic capacity detection element
Wall -mounted slot type 3 screw hole (3.8mm) or duct mounting type CO₂: 0… 50 ° C
Temperature: -20… 70 ° C
Relative humidity (option): 0 ... 95 % RH, no condensation
0… 10V, R> 1kΩ
2… 10V, R> 1kΩ
4 ... 20ma, R <500Ω
0… 10V, R> 1kΩ
2… 10V, R> 1kΩ
4 ... 20ma, R <500Ω
0… 10V, R> 1kΩ
2… 10V, R> 1kΩ
4 ... 20ma, R <500Ω
Automatic school regular or dual channel school regular (optional) by ABC logic IP20 SPDT Relay, 250VAC/30VDC/6A CE Mark, EMC: 2014/30/EU, ROHS: 2011/65/EU, LVD: 2014/35/EU, WEEE: 2012/19/EU 5 Screw terminal block (24V, GND, Co2, RH, T)
Connection wires: 12… 24AWG (0.2-1.5mm²)
3 Screw terminal block (NC, com, No)
Connection wires: 12… 24AWG (0.2-1.5mm²)
Up to 90mA (in 24V) +10 mA per voltage output or 20 mA for each current output Width 77.4mm x height 52.4 mm 150