Collective digital earth leakage detection device LSG-205Handling Company
Hikari Shoko Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | AUTO display | Circuit display | Control power supply voltage | Electric leakage display | Exterior color | Heavy ground fault capacity | Inertial dead time | Insulation resistance | Mass | Maximum value display | Measurement display | Non-operating current | Non-operating power consumption | Number of circuits | Operating power consumption | Operating temperature range | Operating time setting value | Operating time tolerance | Output contact configuration | Output contact switching capacity | Overflow display | Return | Return method | Self-diagnosis display | Sensitivity current setting value | Sensitivity current tolerance range | Test | Withstand voltage | Working voltage range |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
LSG-205 |
Available upon quote | Light emitting diode display (red) ×1 | Light emitting diode display (yellow) ×5 | AC100~200V 50/60Hz DC100V | Light emitting diode display (red) ×5 | Munsell symbol N1.5 | Continuous AC600A, max. 5,000A, 1.2s | 0.1-0.3-0.5s (0.6s) Apply 10A signal or 20 times the sensitivity value, whichever is greater |
20MΩ or more with DC500V megger Between all electrical circuits and the outer box, between electrical circuits, and between open contacts |
Approximately 0.9kg | Light emitting diode display (red) ×1 |
LED numerical display (orange) 3 digits Measurement range: 0.00~1.20A Accuracy: ±10%±1digit Resolution: 0.01A |
0.05-0.1-0.2-0.3-0.4A (0.5A) |
3.1VA (AC100V) 5.2VA (AC200V) 1.5W (DC100V) |
5 circuits |
6.6VA (AC100V) 9A (AC200V) 3.7W (DC100V) |
-20℃~+50℃ | 0.3-0.5-0.8s (1.0s) When 100% signal is applied |
0.3s tap (0.19~0.33s) 0.5s tap (0.42~0.62s) 0.8s tap (0.72~0.90s) 1.0s tap (0.92~1.10s) |
Common operation/abnormality (1 set of NO contacts) Each circuit individually (1 set of NO contacts) |
AC100/200V: 2A (cosφ=1) DC100V: 0.4A (resistive load) AC100/200V: 2A (cosφ=0.4) DC100V: 0.1A (L/R=7ms) |
Measurement display blinking 1.20A | Each circuit or all at once push button switch method |
Output contact: automatic/manual return (batch setting) Electric leakage display: Manual return |
When an error occurs: Err is displayed on the measurement display (automatic recovery), circuit display (yellow) flashes (automatic recovery) | 0.1-0.2-0.4-0.6-0.8A (1.0A) | 51%~100% | Each circuit, push button switch method |
AC2,000V for 1 minute between all electrical circuits and outer box AC1,500V for 1 minute between electrical circuits AC1,000V for 1 minute between open contacts |
AC80~240V DC80~143V |