Product
Unit type earth leakage relay LU-4AHandling Company
Hikari Shoko Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | Control power supply voltage | Exterior color | Frequency | Heavy ground fault capacity | Insulation resistance | Mass | Non-operating current | Operating temperature range | Operating time | Output contact configuration | Output contact return method | Output contact switching capacity 1 | Output contact switching capacity 2 | Power consumption | Sensitivity current setting value | Sensitivity current tolerance range | Test method | Withstand voltage 1 | Withstand voltage 2 | Working voltage range |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
LU-4A |
Available upon quote | AC100/110V or AC200/220V | Munsell symbol N1.5 | 50/60Hz | Continuous AC600A, max. 5,000A, 0.3s | 20MΩ or more at DC500V megger (withstand voltage applied point) | Approximately 0.2kg | 50% of sensitivity current setting value | -20℃~+50℃ | Within 0.15s (100% signal applied) | 3a | Manual return method (by external switch) or automatic return method |
AC110V 2A cosφ=1 0.7A cosφ=0.4 AC200V 0.7A cosφ=1 0.2A cosφ=0.4 |
DC24V 2A L/R=1ms 1A L/R=7ms DC100V 0.35A L/R=1ms 0.15A L/R=7ms |
Constantly 4VA (at 110V AC), 2VA (at 220V AC) Operating 4VA (at 110V AC), 2VA (at 220V AC) |
0.07-0.2-0.4 (A) Internal tap switching | 51~100% | Test switch (inside test hole) |
AC1,500V for 1 minute Between control circuit conductive part and outer box AC1,500V for 1 minute between all control power terminals and control circuit conductive parts |
AC1,000V for 1 minute between control circuit conductive parts AC500V for 1 minute between open contacts of the same control circuit |
AC80~121V or AC160~242V |