■Reliable earth leakage monitoring with two-stage alarm and measurement display ・Compliant with JIS C 8374 earth leakage relay. - Detects earth leakage in low voltage AC circuits in combination with low voltage ZCT. ・Protects in two stages: light leakage and heavy leakage. - Sensitivity current and operating time can be set separately for light leakage and heavy leakage. ・Digital display of current value and maximum value of zero-sequence current. - You can enable/disable the harmonic filter. - Self-diagnosis function automatically detects internal circuit abnormalities. ■Function ・Two-stage alarm Light leakage and heavy earth leakage can be operated separately, allowing two-step protection such as issuing a preventive alarm for light leakage and shutting off for heavy earth leakage. ・Sensitivity current Light leakage can be set in 0.1A increments in the range of 0.2 to 1A, and heavy earth leakage can be set in 1A increments in the range of 2 to 10A. The sensitivity current can be switched finely, making it easier to adjust the control value. ・Operating time Light leakage and heavy earth leakage can be set at 0.1, 0.3, and 0.5 to 1.0 seconds (every 0.5 to 0.1 seconds). The operating time can be changed in detail, making it easier to adjust the management values. ・Measurement display The current value and maximum value of zero-sequence current can be displayed, and the status can be checked numerically. ・Harmonic countermeasures A harmonic filter cuts harmonic components. It can be enabled/disabled as needed, and it is also possible to detect earth leakage including harmonics. ・Self-diagnosis function Internal circuits are automatically tested periodically and equipment abnormalities can be detected at an early stage. Self-diagnosis can be enabled/disabled by setting. ■Features ・Protects low-voltage circuit equipment from electrical leakage. ・Two-stage alarm type for light leakage and heavy earth leakage. ・The two-stage alarm earth leakage relay is a product that can be operated without shutting off in low-voltage equipment where earth leakage current is constantly flowing. - Equipped with a digital display to display measured values. - Automatic/manual return switching method. ・It is a harmonic countermeasure product. (You can switch the harmonic filter ON/OFF.) ・Compliant with "JIS C 8374 Earth Leakage Relay".

  • Product

    Two-stage alarm earth leakage relay LEG-300L

Share this product


30+ people viewing


Free
Since our quotes are free, feel free to use our service.

No Phone Number Required
You won’t have to worry about receiving unnecessary calls.

1 Models of Two-stage alarm earth leakage relay LEG-300L

Product Image Part Number Price (excluding tax) Abnormal display Control power supply voltage Control power supply voltage range Exterior color Frequency Heavy ground fault capacity Inertial dead time (0.3s setting is when filter is OFF) Insulation resistance Mass Measurement display Measurement display Measurement range/accuracy/resolution Non-operating current Operating temperature range Operating time tolerance range (100% sensitivity current applied) Operation display Output contact configuration Output contact return method Output contact switching capacity Power consumption Rated operating time Rated sensitivity current setting value Sensitivity current tolerance range Structure Test Test display Withstand voltage
Two-stage alarm earth leakage relay LEG-300L-Part Number-LEG-300L

LEG-300L

Available upon quote Err" flashes on the measurement display. AC100/110V P0,P1 terminal
AC200/220V P0,P2 terminals
85~110% Body: Black (ABS resin case, flame retardant)
Cover: Colorless and transparent (polycarbonate)
50/60Hz AC600A (continuous)
AC5,000A (operating time maximum setting value or less)
(Light/Heavy) Earth leakage setting value 0.1-0.3-0.5-0.6-0.7-0.8-0.9-1.0s
Inertial dead time ✕-0.1-0.2-0.3-0.4-0.5-0.6-0.7s
20MΩ or more (at DC500V megger)
Between all electrical circuits and the outer box, between electrical circuits, and between open contacts
Approximately 0.4kg 3-digit LED numerical display (orange) 0.00~9.99A, 10.0~13.0A (13.0A flashing display if over 13.0A)
±10%±1digit
0.01A (less than 10A) ,0.1A (more than 10A)
0~50% -20℃~+60℃ 0.10s or less (0.1s filter OFF)
0.11s or less (0.1s filter ON)
-30~+20% of rated operating time (common for filter ON/OFF except 0.1s)
LED (red) Light leakage, heavy leakage
*Reset method is the same as each output contact setting.
1a (light leakage, heavy leakage, 1a each) Automatic/manual AC110V 5A No resistance 2A cosφ=0.4
AC220V 5A No resistance 1.5A cosφ=0.4
DC100V 0.6A No resistance 0.2A L/R=7ms
3VA or less (AC110V) Light leakage 0.1-0.3-0.5-0.6-0.7-0.8-0.9-1.0s
Heavy leakage 0.1-0.3-0.5-0.6-0.7-0.8-0.9-1.0s
Light leakage 0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-1.0A
Heavy leakage 2-3-4-5-6-7-8-9-10A
51~100% Recessed mounting structure Push button switch method, self-diagnosis method 8.8.8." flashes on the measurement display. AC2,000V for 1 minute between all electrical circuits and outer box
AC1,500V for 1 minute between electrical circuits
AC1,000V for 1 minute between open contacts