Product
Earth leakage relay LEG-190L seriesHandling Company
Hikari Shoko Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | Control power supply voltage | Exterior color | Frequency | Heavy ground fault capacity | Inertial dead time | Insulation resistance | Mass | Non-operating current | Operating temperature range | Operating time setting value | Operating time tolerance range (when 100% signal is applied) | Operation display Display method | Operation display Return method | Output contact configuration | Output contact return method | Output contact switching capacity | Power consumption | Sensitivity current setting value | Sensitivity current tolerance range | Test method | Withstand voltage | Working voltage range |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
LEG-190L |
Available upon quote |
AC100/110V AC200/220V |
Munsell symbol N1.5 | 50/60Hz | Continuous AC600A, max. 5,000A, 0.3s | 0.1s | 20MΩ or more with DC500V megger | Approximately 0.8kg | 0.05-0.1-0.2-0.3-0.4 (A) | -20℃~+50℃ | 0.3s | 0.19~0.33s | Light emitting diode display (red) | Automatic/manual return switching | 2c | Automatic/manual return switching |
AC110/220V 5A cosφ=1 2/1.5A cosφ=0.4A DC100V 0.6A L/R=1ms 0.2A L/R=7ms |
3VA at all times, 4VA during operation | 0.1-0.2-0.4-0.6-0.8 (A) | 51%~100% | Test/reset switch (combined) |
Between control circuit conductive part and outer box 2,000V AC for 1 minute Between control circuit conductive parts AC1,500V for 1 minute 1,000V AC for 1 minute between open contacts of the same control circuit |
AC80~121V AC160~242V |