Earth leakage relay LEG-200LHandling Company
Hikari Shoko Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | Control power supply voltage | Control power supply voltage range | Exterior color | Frequency | Heavy ground fault capacity | Inertial dead time | Insulation resistance | Mass | Measurement display | Measurement display Measurement range/resolution | Non-operating current | Operating temperature range | Operating time | Operating time tolerance | Operation display | Output contact configuration | Output contact switching capacity | Power consumption | Return method | Sensitivity current setting value | Sensitivity current tolerance range | Structure | Test | Withstand voltage |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
LEG-200L |
Available upon quote |
AC100/110V P0, P1 terminals AC200/220V P0, P2 terminals |
80~110% | Black (ABS resin) | 50/60Hz | Continuous AC600A, max. 5,000A, 0.3s | 0.1s (when operating time tap is 0.3s) | 20MΩ or more with DC500V megger | Approximately 0.5kg | Light emitting diode numerical display (orange) |
0~1.60A/10mA It will overflow at 1.60A and the number will flash. |
50% or less of setting value | -20℃~+50℃ | 0.1-0.3(s) |
0.1s is less than 0.1s 0.3s is 0.19~0.33s (100% signal applied) |
Light emitting diode display (red) | 2a |
AC110V 5A cosφ=1 2A cosφ=0.4A AC220V 5A cosφ=1 1.5A cosφ=0.4A DC100V 0.6A L/R=1ms 0.2A L/R=7ms |
3.5VA or less (AC110V) | Automatic/manual return switching | 0.2-0.5-1.0 (A) | 51%~100% | Recessed mounting structure | Push button switch method |
AC2,000V for 1 minute AC1,500V for 1 minute AC1,000V for 1 minute |