Detects electrical leakage in low voltage AC circuits. ■Features - Compliant with JIS C 8374. ・It is a harmonic countermeasure product that is not easily affected by noise such as radio waves and surges. ・Compatible with all low-voltage zero-phase current transformers. ・This is an environmentally friendly product (compliant with the European RoHS Directive). ■Operation In combination with a zero-phase current transformer, it provides earth leakage protection for low-voltage distribution lines. If a leakage occurs in the load side circuit after the zero-phase current transformer, an electromotive force will be generated at the secondary terminal of the zero-phase current transformer. After this secondary output is amplified by the amplifier circuit and its magnitude is determined by the level detection circuit, the output contact is activated by the switching circuit, and the operation indicator lamp lights up at the same time. After operation, the automatic return method returns the output contact and turns off the operation indicator when the leakage is eliminated. With the manual reset method, the output contact will not reset and the operation indicator will not turn off until the reset switch is pressed. ■Features -Exposed type earth leakage relay. ・Protects low-voltage circuit equipment from electrical leakage. ・It is a harmonic countermeasure product. - Compliant with "JIS C 8374 Earth Leakage Relay".

  • Product

    Earth leakage relay LEG-107L series

Share this product


40+ people viewing

Last viewed: 7 hours ago


Free
Since our quotes are free, feel free to use our service.

No Phone Number Required
You won’t have to worry about receiving unnecessary calls.

1 Models of Earth leakage relay LEG-107L series

Product Image Part Number Price (excluding tax) Control power supply voltage Frequency Heavy ground fault capacity Inertial dead time Insulation resistance Mass Non-operating current Operating temperature range Operating time Operating time tolerance Operation display Output contact configuration Output contact switching capacity Power consumption Return method Sensitivity current Sensitivity current tolerance range Test Withstand voltage Working voltage range
Earth leakage relay LEG-107L series-Part Number-LEG-107L

LEG-107L

Available upon quote AC100/110V or AC200/220V 50/60Hz Continuous AC600A Max AC5,000A, 0.3 (s) 0.1 (s) 20MΩ or more with DC500V megger
Perform this on the locations where withstand voltage is applied.
Approximately 0.4kg (DC power supply is approximately 0.7kg) 0.05-0.1-0.2-0.3 (A) -20℃~+50℃ 0.3(s) 0.19~0.33 (s) Light emitting diode display (red) 2 sets of A contacts AC100/200V 5A cosφ=1
AC100/200V 2/1.5A cosφ=0.4
DC100V 0.6A L/R=1ms
DC100V 0.2A L/R=7ms
3VA when not operating 4VA when operating Manual return or automatic return (depending on model) 0.1-0.2-0.4-0.6 (A) 51%~100% Push button switch method 2,000V for 1 minute between control circuit conductive part and outer box
1,500V for 1 minute between control circuit conductive parts
1,000V for 1 minute between open contacts of the same control circuit
80~110%