Product
Lightning countermeasures Lightning transformer for power supply Single type ST typeHandling Company
Sankosha Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | Capacity single phase | Capacity three phase | Efficiency single phase | Efficiency three phases | Frequency used | Input/output voltage | Insulation resistance (at DC500V megger) | Insulation type 3 phase | Insulation type single phase | Surge transition rate | Temperature rise limit | Voltage fluctuation rate single phase | Voltage fluctuation rate three-phase | Wiring type (number of phases) | Withstand voltage |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ST type |
Available upon quote | 0.5~30kVA | 1~75kVA |
・0.5kVA or less: 93% or more ・1~2kVA: 93% or more ・3kVA: 95% or more ・5kVA or more: 95% or more |
・7.5kVA or less: 95% or more ・10kVA or more: 97% or more |
50Hz/60Hz | AC100V, AC200V, AC400V, AC100V/200V | 100MΩ or more | 60kVA or less class A, 75kVA or more class B | 2kVA or less class A, 3kVA or more class B | 1/1,000 or less |
・Class A: 55℃ or less (resistance method measurement, at ambient temperature 40℃) ・B class: 75°C or less (resistance method measurement, at ambient temperature of 40°C) |
・0.5kVA or less: 5% or less ・1~2kVA: 4% or less ・3kVA: 3% or less ・5kVA or more: 3% or less |
・7.5kVA or less: 3% or less ・10kVA or more: 2% or less |
Single phase (2 wire, 3 wire), 3 phase 3 wire (delta connection) |
・AC10kV/1 minute, impulse 1.2/50μs/30kV (between input and output) ・AC10kV/1 minute, impulse 1.2/50μs/30kV (between input and ground) ・AC3kV/1 minute (between output and ground) |