Product
Lightning countermeasure SPD for coax B-JP-9Handling Company
Sankosha Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | Allowable power | Current capacity (DC12V) | DC discharge starting voltage (at 100V/s) | Frequency band | Impedance (nominal) | Impulse durability (Category C2) | Impulse durability (Category D1) | Insertion loss (at operating frequency) | Insulation resistance (at DC100V megger) | Mass | Maximum continuous working voltage (250mA or less) | Maximum impulse durability | V.S.W.R (at the frequency used) | Voltage protection level (1.2/50μs, at 10kV) | Voltage protection level (at 1kV/μs) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
B-JP-9 |
Available upon quote | 10W | 3A or less | DC120V or more | DC~3GHz | 75Ω | 8/20μs, 5kA, 10 times | 10/350μs, 2.5kA, 2 times | 0.5dB or less | 100MΩ or more | Approximately 60g | DC50V | 8/20μs, 10kA, once | 1.5 or less | 900V or less | 700V or less |