Product
Lightning protection SPD for Cat6A compatible LAN with deterioration diagnosis LAN-CAT6A-P+II (R)Handling Company
Sankosha Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | AC durability 50Hz, 0.5A, 1s | Bit error rate | Breakdown voltage 100V/s | Compatible line 1 | Compatible line 2 | Compatible line 3 | Connector | Deterioration diagnosis using a dedicated tester | Impulse durability 10/350μs | Impulse durability 8/20μs | Impulse reset DC 60V, 600mA | Insulation resistance DC 60V | Mass | Maximum continuous working voltage Uc | Maximum discharge current 8/20μs | Near-end crosstalk attenuation | Rated current | Transmission band used | Transmission loss (between each line) | Voltage protection level Up 1.2/50μs,10kV |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
LAN-CAT6A-P+II (R) |
Available upon quote | 5 times | 0.01% or less | 160V~300V (between each line and ground) |
10BASE-T: IEEE802.3 100BASE-TX: IEEE802.3u 1,000BASE-T: IEEE802.3ab |
2.5GBASE-T: IEEE802.3bz 5GBASE-T: IEEE802.3bz 10GBASE-T: IEEE802.3an |
PoE: IEEE802.3af PoE+: IEEE802.3at PoE++: IEEE802.3bt |
RJ-45: 8 poles 8 cores | LED on: Normal / LED off: Deteriorated (replacement required) | 2.5kA, 2 times (Category D1) | 5kA, 10 times (Category C2) | Within 30ms (between PoE power supply terminals) | 1,000MΩ or more (between each line and ground) | Approximately 60g | DC 60V (between each line and ground) | 10kA, 10 times (total value between 8 cores and shield to ground) |
1~100MHz: 32.3dB or more ~250MHz: 35.3dB or more ~500MHz: 26.7dB or more |
2,400mA (IEEE802.3af, IEEE802.3at, IEEE802.3bt) | DC~500MHz |
1~100MHz: 1.0dB or less ~250MHz: 2.0dB or less ~500MHz: 4.0dB or less |
500V or less (between each line and ground) |