Product
Lightning countermeasure SPD for communication SPD for Krone terminal SMB-KRAPS1Handling Company
Sankosha Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | AC durability (50Hz, 0.5A) | Deterioration display | Impulse durability (10/350μs, 2.5kA) | Impulse durability (8/20μs, 10kA) | Impulse reset | Insertion loss | Leakage current | Mass | Maximum continuous working voltage UC L-T | Maximum discharge current Imax | Nominal discharge current In | Overload failure mode | Rated current | Series resistance (L1-T1, L2-T2) | Voltage protection level UP (T1, T2-E) | Voltage protection level UP (T1-T2) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
SMB-KRAPS1 |
Available upon quote | 5 times | LED lighting on main unit display (Green: Normal / Yellow: Replacement recommended / Red: Replacement required / All: Deteriorated) | 2 times (Category D1) | 10 times (Category C2) | DC48V, 260mA: 30ms or less | DC~5MHz:1.0dB | DC180V: 10μA or less | Approximately 18g | DC180V | 8/20μs: 10kA (single wire 5kA) | 8/20μs:5kA | Mode 2 | DC100mA | DC100mA: 10Ω or less | 1.2/50μs, 10kV:500V or less | 1.2/50μs, 10kV: 500V or less (in normal mode), 100V or less (in common mode) |