Lightning countermeasures Communication SPD ZP series-ZP-H3 06V JK
Lightning countermeasures Communication SPD ZP series-ZP-H3 12V JK
Lightning countermeasures Communication SPD ZP series-ZP-H3 24V JK
Lightning countermeasures Communication SPD ZP series-ZP-H3 24V JKN
Lightning countermeasures Communication SPD ZP series-ZP-H3 48V JK
Lightning countermeasures Communication SPD ZP series-ZP-N1 JK
Lightning countermeasures Communication SPD ZP series-ZP-N1 JKN
Lightning countermeasures Communication SPD ZP series-Sankosha Co., Ltd.

Lightning countermeasures Communication SPD ZP series
Sankosha Co., Ltd.


About This Product

Communication SPD that protects communication lines and equipment from lightning surges ■Protection line ・Transmission line ・Instrumentation line ・Control line ・RS422 line ・RS485 line ・Telephone line ・DC signal line ■Features ・Thin design allows you to save space ・Maintenance is easy as SPD deterioration can be diagnosed using a dedicated tester. ・You can choose between plug-in type and screw type for the cable connection terminal. - Compatible with JIS category C2 and category D1 ■Environmental conditions ・Usage location: Indoors ・Operating temperature/humidity: -40°C to +70°C/96% or less (no condensation) ・Storage temperature/humidity: -40°C to +70°C/96% or less (no condensation) ・Altitude: 2,000m or less *Other model numbers are available.

  • Product

    Lightning countermeasures Communication SPD ZP series

Share this product


550+ people viewing

Last viewed: 8 hours ago


Free
Since our quotes are free, feel free to use our service.

No Phone Number Required
You won’t have to worry about receiving unnecessary calls.

10 Models of Lightning countermeasures Communication SPD ZP series

Items marked with have different values depending on the model number.

Click on the part number for more information about each product

Product Image Part Number Price (excluding tax) AC durability (50Hz, 0.5A, 1s) DC discharge starting voltage (100V/s) Deterioration display (using a dedicated tester) Impulse durability (10/350μs, 2.5kA) Impulse durability (8/20μs, 5kA) Impulse reset (DC48V, 260mA) Insertion loss Insulation resistance Leakage current Main uses Mass Maximum continuous working voltage UC Maximum discharge current Imax (10/350μs) D1 Maximum discharge current Imax (8/20μs) C2 Overload failure mode Rated current Series resistance Type Voltage protection level UP
Lightning countermeasures Communication SPD ZP series-Part Number-ZP-H3 06V JK

ZP-H3 06V JK

Available upon quote 5 times - LED on: Normal / LED off: Deteriorated (replacement required) 2 times (Category D1) 10 times (Category C2) - DC~400kHz: 1.0dB or less - - Transmission/instrumentation line Approximately 70g DC9V 2kA (1kA x 2 times) 10kA (5kA x 2 times) Mode 1 DC400mA DC5V:5Ω±10% Plug terminal type 1.2/50μs, 10kV: 80V or less
Lightning countermeasures Communication SPD ZP series-Part Number-ZP-H3 12V JK

ZP-H3 12V JK

Available upon quote 5 times - LED on: Normal / LED off: Deteriorated (replacement required) 2 times (Category D1) 10 times (Category C2) - DC~400kHz: 1.0dB or less - - Transmission/instrumentation line Approximately 70g DC13.5V 2kA (1kA x 2 times) 10kA (5kA x 2 times) Mode 1 DC100mA 100mA:5Ω±10% Plug terminal type 1.2/50μs, 10kV: 100V or less
Lightning countermeasures Communication SPD ZP series-Part Number-ZP-H3 24V JK

ZP-H3 24V JK

Available upon quote 5 times - LED on: Normal / LED off: Deteriorated (replacement required) 2 times (Category D1) 10 times (Category C2) - DC~400kHz: 1.0dB or less - DC27V: 5μA or less Transmission/instrumentation line Approximately 70g DC27V 2kA (1kA x 2 times) 10kA (5kA x 2 times) Mode 1 DC100mA 100mA:5Ω±10% Plug terminal type 1.2/50μs, 10kV: 120V or less
Lightning countermeasures Communication SPD ZP series-Part Number-ZP-H3 24V JKN

ZP-H3 24V JKN

Available upon quote 5 times - LED on: Normal / LED off: Deteriorated (replacement required) 2 times (Category D1) 10 times (Category C2) - DC~400kHz: 1.0dB or less - DC27V: 5μA or less Transmission/instrumentation line Approximately 70g DC27V 2kA (1kA x 2 times) 10kA (5kA x 2 times) Mode 1 DC100mA 100mA:5Ω±10% Screw terminal type 1.2/50μs, 10kV: 120V or less
Lightning countermeasures Communication SPD ZP series-Part Number-ZP-H3 48V JK

ZP-H3 48V JK

Available upon quote 5 times - LED on: Normal / LED off: Deteriorated (replacement required) 2 times (Category D1) 10 times (Category C2) - DC~400kHz: 1.0dB or less - DC52V: 5μA or less Transmission/instrumentation line Approximately 70g DC52V 2kA (1kA x 2 times) 10kA (5kA x 2 times) Mode 1 DC100mA 100mA:5Ω±10% Plug terminal type 1.2/50μs, 10kV: 140V or less
Lightning countermeasures Communication SPD ZP series-Part Number-ZP-N1 JK

ZP-N1 JK

Available upon quote 5 times 180V or more LED on: Normal / LED off: Deteriorated (replacement required) 2 times (Category D1) 10 times (Category C2) 30ms or less DC~1MHz: 1.0dB or less DC150V: 10MΩ or more - Transmission/instrumentation line Approximately 70g DC150V 1kA (0.5kA×2 times) 10kA (5kA x 2 times) Mode 1 DC3A - Plug terminal type 1.2/50μs, 4kV: 50V or less (between L1 and L2), 1,000V or less (between T1, T2 and G)
Lightning countermeasures Communication SPD ZP series-Part Number-ZP-N1 JKN

ZP-N1 JKN

Available upon quote 5 times 180V or more LED on: Normal / LED off: Deteriorated (replacement required) 2 times (Category D1) 10 times (Category C2) 30ms or less DC~1MHz: 1.0dB or less DC150V: 10MΩ or more - Transmission/instrumentation line Approximately 70g DC150V 1kA (0.5kA×2 times) 10kA (5kA x 2 times) Mode 1 DC3A - Screw terminal type 1.2/50μs, 4kV: 50V or less (between L1 and L2), 1,000V or less (between T1, T2 and G)
Lightning countermeasures Communication SPD ZP series-Part Number-ZP-NM JK

ZP-NM JK

Available upon quote 5 times 180V or more LED on: Normal / LED off: Deteriorated (replacement required) 2 times (Category D1) 10 times (Category C2) 30ms or less DC~1MHz: 1.0dB or less DC150V: 10MΩ or more - Transmission/instrumentation line Approximately 70g DC150V 1kA (0.5kA×2 times) 10kA (5kA x 2 times) Mode 1 - - Plug terminal type 1.2/50μs, 4kV: 50V or less (between L1 and L2), 1,000V or less (between T1, T2 and G)
Lightning countermeasures Communication SPD ZP series-Part Number-ZP-NM JKN

ZP-NM JKN

Available upon quote 5 times 180V or more LED on: Normal / LED off: Deteriorated (replacement required) 2 times (Category D1) 10 times (Category C2) 30ms or less DC~1MHz: 1.0dB or less DC150V: 10MΩ or more - Transmission/instrumentation line Approximately 70g DC150V 1kA (0.5kA×2 times) 10kA (5kA x 2 times) Mode 1 - - Screw terminal type 1.2/50μs, 4kV: 50V or less (between L1 and L2), 1,000V or less (between T1, T2 and G)
Lightning countermeasures Communication SPD ZP series-Part Number-ZP-K2 JK

ZP-K2 JK

Available upon quote - 280V or more LED on: Normal / LED off: Deteriorated (replacement required) 2 times (Category D1) 10 times (Category C2) - DC~10MHz: 1.0dB or less DC180V: 100MΩ or more - Control line Approximately 70g DC180V, AC140V 1kA (0.5kA×2 times) 10kA (5kA x 2 times) Mode 1 3A - Plug terminal type 1.2/50μs, 4kV: 800V or less

Click on the part number for more information about each product