Product
Precision air conditioner Precision air conditioner CFC-free/energy-saving model Temperature control type PAU-GR3000SEHandling Company
Apiste Co., Ltd.Categories
Usage Scenarios
Electronics & Electrical Use / Chemical Industry Use / Pharmaceutical & Medical UseProduct Image | Part Number | Price (excluding tax) | Air duct connection diameter (mm) | Cooling capacity (W) | Cooling method | Current consumption (A) | Dehumidification capacity (g/kg (DA) ) | Drain outlet | Exhaust air volume (㎥/min) | External dimensions (mm) | Frame drain | Heating capacity (W) | Main unit air volume (㎥/min) | Mass (kg) | Noise (dB (A) ) | Operating ambient humidity (%RH) | Operating ambient temperature (℃) | Output/control attention output | Output/main unit abnormal output | Output/operating output | Paint color | Possible temperature setting range (℃) | Power consumption (W) | Protection function | Rated voltage (V) | Refrigerant | Temperature control accuracy (℃) | Temperature control range (℃) | Type |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
PAU-GR3000SE |
Available upon quote | Φ150 | 3,000 (3,500) | Air-cooled | 4.5 (rated) /6.0 (MAX) | 12.9 (Achieved dew point temperature: 3.5℃ DP or less) | 20A (Rc3/4) | 10 | H1,280×W450×D700 | 15A (Rc1/2) | 1,180 |
10.0 (in normal mode/energy saving mode) 3.0 (in dry mode) |
110 | 66 | 15~85 (Humidity change gradient: within 5%/1h) (No condensation) | 15~35 (Temperature change gradient: within 1℃/1h) | No voltage (AC250V/2A/resistive load) *A contact or B contact can be selected | No voltage (AC250V/2A/resistive load) *A contact or B contact can be selected | No voltage (AC250V/2A/resistive load) *A contact or B contact can be selected | Munsell N-87 gray equivalent | 0~50 | 1,145 (rated) /1,450 (MAX) | Earth leakage breaker (15A 30mA) / Voltage abnormality detection / Rotation speed abnormality detection / Residual operation function after stop / Inverter protection function / Cooler antifreeze function / High pressure side high temperature abnormality | Three phase AC200~240 | R1234yf 760g | ±0.1 | 20~30 | Temperature control type |