Product
Heat Countermeasure Equipment Control Panel Cooler Freon Special Specifications Side Mounting Type ENC-NW2200LHandling Company
Apiste Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | Cooling capacity (W) | Cooling water/flow rate (ℓ/min) | Cooling water/pressure (Mpa) | Cooling water/temperature range (℃) | Current consumption: MAX (A) | Current consumption: Rated (A) | Display | External dimensions (mm) | External output | Mass (kg) | Mounting type | Noise (dB (A) ) | Noise resistance | Operating ambient humidity (%RH) | Operating ambient temperature (℃) | Paint color | Power consumption: MAX (W) | Power consumption: Rated (W) | Rated voltage (V) | Refrigerant/filling amount (g) | Set temperature range (℃) | Starting current (A) | Vibration resistance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ENC-NW2200L |
Available upon quote | 2,000/2,200 | 8 | 0.2~0.5 | 10~40 | 3.3/3.0 | 3.0/2.5 | Panel temperature/error display LED/RUN LED | H1,000×W400×D230 | Alarm output (no-voltage A contact: 250V 2A resistive load) | 43 | Side mounting | 62/62 | LEVEL4 by fast transient/burst immunity test | 10~80 (no condensation) | 20~55 | Munsell 5Y7/1 Light beige equivalent color | 690/810 | 490/570 | Three phase AC200 | R134a 200g | 25~45 | 31/30 | Frequency: 5Hz Total amplitude: 20mm |