Product
Industrial blower unit heater standard type (for hot water) KUV-W Vertical blow down diffusion range adjustable typeHandling Company
Kamakura Seisakusho Co., Ltd.Categories
Items marked with have different values depending on the model number.
Click on the part number for more information about each product
Product Image | Part Number | Price (excluding tax) | Air flow rate (50Hz/60Hz) | Average wind speed (50Hz/60Hz) | Blow air temperature (50Hz/60Hz) | Fan diameter | Head loss (50Hz/60Hz) | Heating capacity (50Hz/60Hz) | Hot water piping diameter | Hot water temperature | Motor specifications | Noise (50Hz/60Hz) | Power supply | Required amount of hot water (50Hz/60Hz) | Suction air temperature | Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
KUV-142W |
Available upon quote | 35/40㎥/min | 5.4/6.2m/s | 45/44℃ | 35cm | 1.13/1.30mH2O | 21.5/23.8kW |
Entrance (top): 32A Exit (bottom): 32A |
Inlet: 80℃ Outlet: 75℃ |
Number of poles: 4P Output: 0.1kW |
57/59dB |
Number of phases: 3φ Voltage: 200V |
62/68ℓ/min | 15℃ | 42kg | |
KUV-182W |
Available upon quote | 54/58㎥/min | 5.2/5.6m/s | 44/43℃ | 45cm | 2.43/2.62mH2O | Heating capacity (50Hz/60Hz) |
Entrance (top): 32A Exit (bottom): 32A |
Inlet: 80℃ Outlet: 75℃ |
Number of poles: 6P Output: 0.25kW |
59/60dB |
Number of phases: 3φ Voltage: 200V |
92/95ℓ/min | 15℃ | 54kg | |
KUV-202W |
Available upon quote | 86/99㎥/min | 6.7/7.8m/s | 43/41℃ | 50cm | 1.82/2.06mH2O | Heating capacity (50Hz/60Hz) |
Entrance (top): 40A Outlet (bottom): 40A |
Inlet: 80℃ Outlet: 73℃ |
Number of poles: 6P Output: 0.4kW |
63/64dB |
Number of phases: 3φ Voltage: 200V |
101/108ℓ/min | 15℃ | 75kg | |
KUV-242W-E3 |
Available upon quote | 148/163㎥/min | 7.7/8.4m/s | 39/38℃ | 60cm | 2.56/2.84mH2O | 72.7/76.9kW |
Entrance (top): 50A Outlet (bottom): 50A |
Inlet: 80℃ Outlet: 73℃ |
Number of poles: 6P Output: 0.75kW |
69/71dB |
Number of phases: 3φ Voltage: 200V |
149/157ℓ/min | 15℃ | 99kg | |
KUV-302PW-E3 |
Available upon quote | 250/270㎥/min | 8.4/9.1m/s | 37/36℃ | 75cm | 3.25/3.40mH2O | 112.0/117.0kW |
Entrance (top): 50A Outlet (bottom): 50A |
Inlet: 80℃ Outlet: 72℃ |
Number of poles: 6P Output: 1.5kW |
77/78dB |
Number of phases: 3φ Voltage: 200V |
201/210ℓ/min | 15℃ | 135kg | |
KUV-302NW |
Available upon quote | 200/230㎥/min | 6.7/7.7m/s | 40/38℃ | 77cm | 2.96/3.15mH2O | 101.0/108.0kW |
Entrance (top): 50A Outlet (bottom): 50A |
Inlet: 80℃ Outlet: 72℃ |
Number of poles: 8P Output: 1.5kW |
66/71dB |
Number of phases: 3φ Voltage: 200V |
181/193ℓ/min | 15℃ | 142kg |
Click on the part number for more information about each product