Ground fault voltage relay LVG-7S series-LVG-7S
Ground fault voltage relay LVG-7S series-Hikari Shoko Co., Ltd.

Ground fault voltage relay LVG-7S series
Hikari Shoko Co., Ltd.


About This Product

■Ground fault voltage relay device for low voltage ungrounded circuits This is a ground-fault directional relay device that is used in combination with a zero-phase capacitor (ZPC-2C) to protect low-voltage power lines below AC440V from ground faults. The detected voltage element can be supplied to the LDG-71S series as an MN signal. This product is a special product for low voltage ungrounded electrical circuits. Please note that there are also special products with the same format but different specifications. ■Combination - Not compatible with zero-phase capacitor (ZPC-2C). Be sure to use the same product number in combination. ・Can also be used in combination with a ground fault directional relay. Please use as necessary. - You can also combine AC power models and DC power models. - Can also be combined with ground fault directional relay devices LDG-21S and LDG-21S-DC1 (both special products for low-voltage ungrounded circuits and discontinued products). However, it is not possible to mix and match AC and DC power models. ■Features ・This is a custom-made product for low-voltage electrical circuits below AC440V. ・Used in combination with zero-phase capacitor (ZPC-2C).

  • Product

    Ground fault voltage relay LVG-7S series

Share this product


40+ people viewing

Last viewed: 8 hours ago


Free
Since our quotes are free, feel free to use our service.

No Phone Number Required
You won’t have to worry about receiving unnecessary calls.

1 Models of Ground fault voltage relay LVG-7S series

Product Image Part Number Price (excluding tax) Commercial frequency withstand voltage Control voltage Effect of control voltage Effect of temperature Exterior color Frequency Insulation resistance Mass Number of connected LDG-71S series units Operating temperature range Operating time error 150% of the set voltage value Operating time setting value Operating value error Operating voltage setting value % of full earth fault voltage/line voltage AC*V Operation display Display method Operation display Return method Output contact configuration Output contact return method Output contact switching capacity Power consumption Always Power consumption during operation Test method Vibration
Ground fault voltage relay LVG-7S series-Part Number-LVG-7S

LVG-7S

Available upon quote 2,000V AC for 1 minute between the relay's electrical circuit and the outer box AC110V
Working voltage range AC90~120V
At 90~120V AC or 80~143V DC (relative to actual measurements under standard conditions)
Operating voltage ±10%, operating time ±10% (0.05s is 0.1s or less)
At -20℃~+60℃ (relative to actual measurements under standard conditions)
Operating voltage ±15%, operating time ±10% (0.05s is 0.1s or less)
Munsell symbol N1.5 50/60Hz 20MΩ or more between the relay's electrical circuit and the outer box using a 500V DC megger Approximately 1.0kg 30 units -20℃~+60℃ 0.05: 0.1 or less
0.2: 0.1~0.2
0.5: 0.4~0.6
0.8: 0.7~0.9
1.0: 0.95~1.1
0.05-0.2-0.5-0.8-1.0 (s) ±25% 5-10-15-20-30/420
10-20-30-40-50/380
10-20-30-40-50/300
10-20-30-40-50/210
20-30-40-50-60/105
Light emitting diode display (red) Automatic return method 2a Automatic return method AC110V 5A cosφ=1 2A cosφ=0.4
DC24V 5A L/R=1ms 2A L/R=7ms
DC100V 0.6A L/R=1ms 0.2A L/R=7ms
AC110V 4.4VA AC110V 5.5VA Test switch Double amplitude 0.4mm 16.7Hz
Front/back, left/right, up/down, 600s in each direction

Customers who viewed this product also viewed

Other products of Hikari Shoko Co., Ltd.


View more products of Hikari Shoko Co., Ltd.