Ior detection method Collective type insulation condition monitoring device with earth leakage direction function-LSIG-8
Ior detection method Collective type insulation condition monitoring device with earth leakage direction function-Hikari Shoko Co., Ltd.

Ior detection method Collective type insulation condition monitoring device with earth leakage direction function
Hikari Shoko Co., Ltd.


About This Product

This is an 8-circuit type Ior detection type insulation condition monitoring device. In addition to having the same functions as LIG-11 for 8 circuits, it can store and display numerical data from the past 10 alarm operations. ■Features ・Ior type insulation monitoring device. Up to 8 circuits can be monitored. ・Equipped with analog output (DC1-5V) and digital output (EIA-485) as standard. ・You can check the current value and maximum value using the measurement display function. ・The earth leakage monitoring section has a directional function to prevent accidents.

  • Product

    Ior detection method Collective type insulation condition monitoring device with earth leakage direction function

Share this product


30+ people viewing

Last viewed: 20 hours ago


Free
Since our quotes are free, feel free to use our service.

No Phone Number Required
You won’t have to worry about receiving unnecessary calls.

1 Models of Ior detection method Collective type insulation condition monitoring device with earth leakage direction function

Product Image Part Number Price (excluding tax) Abnormal display Alarm contact Abnormal alarm Alarm contact insulation alarm Ambient temperature range Control power supply voltage Earth leakage monitoring section Sensitivity current setting value Earth leakage monitoring section Sensitivity current tolerance range Earth leakage monitoring section inertia non-operation time Earth leakage monitoring section non-operating current Earth leakage monitoring unit operating time allowable range Earth leakage monitoring unit operating time setting value Elevation Heavy ground fault capacity Insulation condition monitoring section Sensitivity current setting value Insulation condition monitoring section Sensitivity current tolerance range Insulation condition monitoring unit operating time setting value Insulation condition monitoring unit operating time tolerance range Insulation resistance Measurement display Abnormal display Measurement display Io current (current location, maximum value) Measurement display Ior current (current location, maximum value) Monitoring circuit setting Monitoring line frequency Operation display Power consumption Relative humidity Test method When recording operating values Withstand voltage Working voltage range
Ior detection method Collective type insulation condition monitoring device with earth leakage direction function-Part Number-LSIG-8

LSIG-8

Available upon quote Light emitting diode display (red): Automatic recovery method 1 set of a contacts (terminal symbols a1-c1,2): automatic reset method (shared with insulation monitoring alarm and common terminals (c1,2)) 1 set of a contacts (terminal symbols a2-c1,2): automatic/manual reset switching (abnormal alarm and common terminals (c1,2) are shared) -10℃~+50℃ AC100V Lock-0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-1.0 (A)
*Can be set individually for each circuit.
*It will not be monitored when set to lock.
51~100% 0.1-0.3-0.4-0.5-0.6-0.7-0.8-0.9-1.2-1.4-1.6-1.7 (s) 0.1-0.15-0.2-0.25-0.3-0.35-0.4-0.45-0.5 (A) When a current of 100% of the current setting value is applied
0.3-0.4-0.5-0.6-0.7-0.8-0.9-1.0-1.3-1.5-1.8 (s): +0.15~-0.1s
2.0s: +0~-0.3s
0.3-0.4-0.5-0.6-0.7-0.8-0.9-1.0-1.3-1.5-1.8-2.0 (s)
*Can be set individually for each circuit.
2,000m or less Continuous: AC600A Lock-30-35-40-45-50-55-60-65-70-75-80-85-90-95-100 (mA)
*Can be set individually for each circuit.
*It will not be monitored when set to lock.
Within ±10% at current setting value of 50mA 5-10-20-30-40 (s)
*Can be set individually for each circuit.
When a current of 130% of the current setting value is applied
5s: ±1s
10-20-30-40 (s): ±10%
20MΩ or more using a 500V DC megger (conducted at locations where withstand voltage is applied) Displays an error when there is an abnormality that interferes with the monitoring status AC0A~1.1A 50/60Hz (automatic selection and manual selection) AC3mA~999mA 50/60Hz (automatic selection and manual selection) Lock-1φ2W-1φ3W-3φY-3φDu-3φDw (Electrical line voltage used is AC440V or less) 50/60Hz (manual switching)
Control power frequency is also the same
Isolation operation LED display (red): Automatic/manual return switching
Earth leakage operation LED display (red): Automatic/manual return switching
Always: 11VA or less
Operating: 13VA or less
45~85% Test switch
Automatic self-diagnosis method (switchable with/without self-diagnosis)
The Ior value/Io value at the time of operation (values ​​up to 10 times before) is recorded and displayed by manual selection. AC2,000V for 1 minute between control circuit conductive part and outer box
AC1,500V for 1 minute Between conductive parts of control circuits (excluding between input circuits)
1,000V AC for 1 minute between open contacts of the same control circuit
85~110%