Product
Ior detection method Insulation condition monitoring device with earth leakage direction functionHandling Company
Hikari Shoko Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | Abnormal display | Alarm contact Abnormal alarm | Alarm contact Earth leakage alarm | Alarm contact insulation alarm | Ambient temperature range | Control power supply voltage | Earth leakage monitoring section Sensitivity current setting value | Earth leakage monitoring section Sensitivity current tolerance range | Earth leakage monitoring section inertia non-operation time | Earth leakage monitoring section non-operating current | Earth leakage monitoring unit operating time allowable range | Earth leakage monitoring unit operating time setting value | Elevation | Heavy ground fault capacity | Insulation condition monitoring section Sensitivity current setting value | Insulation condition monitoring section Sensitivity current tolerance range | Insulation condition monitoring unit operating time setting value | Insulation condition monitoring unit operating time tolerance range | Insulation resistance | Measurement display Abnormal display | Measurement display Io current (current location, maximum value) | Measurement display Ior current (current location, maximum value) | Monitoring circuit setting | Monitoring line frequency | Operation display | Power consumption | Relative humidity | Test method | Withstand voltage | Working voltage range |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
LIG-11 |
Available upon quote | Light emitting diode display (red): Automatic recovery method |
1 set of a contacts (terminal symbols a1-c1,2): automatic reset method (shared with insulation monitoring alarm and common terminals (c1,2)) (If the earth leakage alarm contact was closed in advance, the abnormality contact will not be closed.) |
1 set of a contacts (terminal symbol a3-c3): automatic/manual return switching (If the abnormality alarm contact was closed in advance, the earth leakage alarm contact will not be closed.) |
1 set of a contacts (terminal symbols a2-c1,2): automatic reset method (abnormal alarm and common terminals (c1,2) are shared) (If the earth leakage alarm contact or abnormality alarm contact has been closed in advance, the insulation alarm contact will not be closed.) |
-10℃~+50℃ | AC100V | 0.2-0.4-0.6-0.8-1.0 (A) | 51~100% | 0.1-0.3-0.5-0.8-1.6 (s) | 0.1-0.2-0.3-0.4-0.5 (A) |
When a current of 100% of the current setting value is applied 0.3-0.5-0.8-1.0 (s): +0.15~-0.1s 2.0s: +0~-0.3s |
0.3-0.5-0.8-1.0-2.0 (s) | 2,000m or less | Continuous: AC600A Maximum: AC5,000A 2.0s | 30-40-50-60-70 (mA) | Within ±10% at current setting value of 50mA | 5-10-20-30-40 (s) |
When a current of 130% of the current setting value is applied 5-10 (s): ±1s 20-30-40 (s): ±10% |
20MΩ or more using a 500V DC megger (conducted at locations where withstand voltage is applied) | Displays an error when there is an abnormality that interferes with the monitoring status | AC0A~1.1A (automatic selection and manual selection) | AC3mA~999mA (automatic selection and manual selection) | 1φ2W-1φ3W-3φY-3φ△ (Used circuit voltage is AC440V or less) |
50/60Hz (manual switching) Control power frequency is also the same |
Isolation operation LED display (red): Automatic/manual return switching Earth leakage operation Magsign display (orange during operation): Manual return method |
Always: 6VA or less Operating: 7VA or less |
45~85% |
Test switch Automatic self-diagnosis method |
AC2,000V for 1 minute between control circuit conductive part and outer box AC1,500V for 1 minute Between conductive parts of control circuits (excluding between input circuits) 1,000V AC for 1 minute between open contacts of the same control circuit |
80~110% |