Product
High voltage ground fault relay LEG-107Handling Company
Hikari Shoko Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | Commercial frequency withstand voltage | Control voltage | Excessive ground fault resistance | Exterior color | Frequency | Inertial characteristics | Insulation resistance | Mass | Non-operational characteristics | Operating current setting value | Operating current tolerance | Operating temperature range | Operating time characteristics | Operating time setting value | Operation display Display method | Operation display Return method | Output contact closing capacity | Output contact configuration | Output contact switching capacity | Power consumption Always | Power consumption during operation | Test method |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
LEG-107 |
Available upon quote |
Between the relay's electrical circuit and the outer box AC2,000V 1 minute question |
AC110V Working voltage range AC90~120V | AC120A continuous | Munsell symbol N1.5 | 50/60Hz | Apply 400% of setting current value, 0.05s |
Between the relay's electrical circuit and the outer box 20MΩ or more with DC500V megger |
Approximately 0.4kg | No operation at 80% of the set current value | 0.1-0.2-0.4-0.6 (A) | ±10% of the setting current value | -20℃~+50℃ |
0.1~0.3s (130% of setting current value applied) 0.1~0.2s (400% of setting current value applied) |
0.2s | Mag sign display (during operation: orange) | Manual return method (return switch) | DC140V 5A 0.2s (L/R=7ms) | 2a |
AC110V 5A, cosφ=1 2A, cosφ=0.4 DC100V 0.6A,L/R=1ms 0.2A,L/R=7ms |
AC110V 3VA | AC110V 4VA | Test switch |