Product
High voltage ground fault relay LEG-191Handling Company
Hikari Shoko Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | Commercial frequency withstand voltage | Control voltage | Excessive ground fault resistance | Exterior color | Frequency | Inertial characteristics | Insulation resistance | Mass | Non-operational characteristics | Operating current setting value | Operating current tolerance | Operating temperature range | Operating time characteristics | Operating time setting value | Operation display Display method | Operation display Return method | Output contact closing capacity | Output contact configuration | Output contact return method | Output contact switching capacity | Output contact usage | Power consumption Always | Power consumption during operation | Test method | Working voltage range |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
LEG-191 |
Available upon quote |
Between all electrical circuits and outer box: AC2,000V for 1 minute Between electrical circuits: AC2,000V for 1 minute Contact circuit open between contacts: AC1,000V for 1 minute |
AC110V | AC120A continuous | Munsell symbol N1.5 | 50/60Hz | Inoperable when 400% of the setting current value is applied for 0.05s | 20MΩ or more with DC500V megger | Approximately 1.2kg | No operation at 80% of the set current value | 0.1-0.2-0.4-0.6-0.8 (A) | ±10% of the setting current value | -20℃~+50℃ |
0.1~0.3s (130% of setting current value applied) 0.1~0.2s (400% of setting current value applied) |
0.2s | Mag sign display (during operation: orange) | Manual return method (combined test/return switch) | DC140V 5A 0.2s (L/R=7ms) | S1,S2,T1,T2,O1,O2,1a (for alarm) | Automatic/manual return switching (when set to manual return, doubles as test/return switch) |
AC110V/220V 5A, cosφ=1 2/1.5A, cosφ=0.4 DC100V 0.6A,L/R=1ms 0.2A,L/R=7ms |
For current tripping | 3VA | 4VA | Test/reset switch (combined) | AC90~120V |