Product
Ground fault voltage relay LVG-7E seriesHandling Company
Hikari Shoko Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | Commercial frequency withstand voltage | Control voltage | Exterior color | Frequency | Insulation resistance | Mass | Operating temperature range | Operating time error 150% of the set voltage value | Operating time setting value | Operating voltage setting (% of full earth fault voltage) | Operating voltage tolerance | Operation display Display method | Operation display Return method | Output contact closing capacity | Output contact configuration | Output contact return method | Output contact switching capacity | Power consumption Always | Power consumption during operation | Test method |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
LVG-7E |
Available upon quote |
Between the electric circuit and the outer box AC2,000V for 1 minute |
AC110V, AC90~120V AC220V, AC180~240V |
Black (ABS resin) | 50/60Hz |
Between the electric circuit and the outer box 20MΩ or more with DC500V megger |
Approximately 0.9kg | -20℃~+60℃ |
Setting value 0.1s: 0.1 or less Setting value 0.2s: 0.1~0.2 Setting value 0.5s: 0.4~0.6 Setting value 0.8s: 0.7~0.9 Setting value 1.0s: 0.95~1.1 |
0.1-0.2-0.5-0.8-1.0 (s) | 2.5-5-7.5-10-15 (%) | ±25% of the set voltage value | Light emitting diode display (red) |
Automatic/manual return switching Test/reset switch (also used) when returning manually |
DC140V 5A 0.2s, L/R=7ms | 2c |
Automatic/manual return switching Test/reset switch (also used) when returning manually |
AC110V/220V 5A, cosφ=1 2/1.5A, cosφ=0.4 DC100V 0.6A,L/R=1ms 0.2A,L/R=7ms |
4.4VA (AC110,AC220V) | 5.5VA (AC110,AC220V) | Test/reset switch (combined) |