Digital type PC grounding system 1-circuit ground fault direction relay LDG-83P series-LDG-83P
Digital type PC grounding system 1-circuit ground fault direction relay LDG-83P series-Hikari Shoko Co., Ltd.

Digital type PC grounding system 1-circuit ground fault direction relay LDG-83P series
Hikari Shoko Co., Ltd.


About This Product

This is a ground fault directional relay mainly used for single circuits. Zero-sequence voltage and zero-sequence current can be detected. Voltage elements can be supplied to the LDG-81P series as MN signals. ■Features ・This is a digital ground fault directional relay intended for ground fault protection in PC grounding type electrical circuits (AC6,600V 60Hz). -For 1 circuit. ・You can check the current value and maximum value using the measurement display function. - Self-diagnosis function automatically detects internal circuit abnormalities. - Compliant with "JIS C 4609 Earth fault directional relay device for high voltage power receiving".

  • Product

    Digital type PC grounding system 1-circuit ground fault direction relay LDG-83P series

Share this product


20+ people viewing

Last viewed: 12 hours ago


Free
Since our quotes are free, feel free to use our service.

No Phone Number Required
You won’t have to worry about receiving unnecessary calls.

1 Models of Digital type PC grounding system 1-circuit ground fault direction relay LDG-83P series

Product Image Part Number Price (excluding tax) Commercial frequency withstand voltage Control voltage Effect of control voltage Effect of temperature Excessive ground fault resistance Exterior color Frequency Insulation resistance Mass Measurement display Number of connected devices Operating current setting value Operating phase error Operating temperature range Operating time error 400% of the set current value Operating time error: 130% of the set current value Operating time setting value Operating value error Operating voltage setting (% of full earth fault voltage) Operation display Display method Operation display Return method Output contact closing capacity Output contact configuration Output contact return method Output contact switching capacity Overflow display Power consumption Always Power consumption during operation Test method Vibration
Digital type PC grounding system 1-circuit ground fault direction relay LDG-83P series-Part Number-LDG-83P

LDG-83P

Available upon quote Between the relay's electric circuit and the outer box: AC2,000V for 1 minute
Between electrical circuits (excluding between input circuits): AC2,000V for 1 minute
Contact circuit open terminal: 1,000V AC for 1 minute
AC110V, working voltage range AC90~120V At AC90~120V (relative to actual measurements under standard conditions)
Operating current ±5%, operating phase ±5°,
Operating voltage ±10%, operating time ±10%
At -20℃~+60℃ (relative to actual measurements under standard conditions)
Operating current ±10%, operating phase ±15°, operating voltage ±15%, operating time ±10%
AC120A continuous Munsell symbol N1.5 60Hz Between the electric circuit and the outer box
20MΩ or more with DC500V megger
Approximately 1.2kg Io, IoMAX AC0.02A~1.10A, Vo, VoMAX 1.0%~20.0%
Error display: Displays an error when there is an error that interferes with the monitoring status.
30 units (LDG-81P) 0.1-0.2-0.4-0.6-1.0 (A) Vo = 150% voltage of the setting voltage value, Io = 1,000% current of the setting current value
(Leading) 135°±45° (Lagging) 60°±15°
-20℃~+60℃ Setting value 0.2s: 0.1~0.2
Setting value 0.5s: 0.4~0.6
Setting value 0.8s: 0.7~0.9
Setting value 1.0s: 0.95~1.1
Setting value 0.2s: 0.1~0.3
Setting value 0.5s: 0.4~0.65
Setting value 0.8s: 0.7~0.95
Setting value 1.0s: 0.95~1.15
0.2-0.5-0.8-1.0 (s) Io: ±10%
Vo: ±25%
5-7.5-10-12.5-15 (%) Mag sign display (during operation: orange)
Io, Vo operation display: Light emitting diode display (red)
Magsign display: Manual return method (combined test/return switch)
Io, Vo operation display: Automatic return method
For voltage trip and alarm DC140V 5A 0.2s (L/R=7ms) For voltage tripping and alarm 2a Automatic/manual return switching (combined as test/return switch when manual return is set) AC110V 5A, cosφ=1 2A, cosφ=0.4
DC24V 5A,L/R=1ms 2A,L/R=7ms
DC100V 0.6A,L/R=1ms 0.2A,L/R=7ms
Measurement display blinking (Io: 1.10A, Vo: 20.0%) AC110V 2.6VA AC110V 3.5VA Test/reset switch (combined)
Automatic self-diagnosis method
Double amplitude 0.4mm 16.7Hz
Front/back, left/right, up/down, 600s in each direction