This product is registered by LAPP JAPAN Co., Ltd..
About This Product
Fixed use, direct burial; PVC cable with single-core aluminum conductor.
■Scope of application
- Power and control cables for fixed use in the following applications.
- Indoor and outdoor use.
- Compliant with VDE standard HD603/VDE0276-603-Part3-G (point 4) for burial without additional suitable underground protection, direct burial of PVC cables: typical minimum installation depth of 0.6 m, but under load requires at least 0.8m.
- Conforms to VDE standard HD603/VDE0276-603-Part 3-G (Point 4), which stipulates PVC cables for direct burial in concrete at temperatures below the maximum cable operating temperature +70°C.
■Features
・Flammability characteristics - Flame retardant (IEC60332-1-2 compliant).
- The maximum tensile strain of the aluminum conductor during installation is 30N/mm2 in accordance with HD603/VDE0276-603: Part 1 Appendix A.4.12 and Part 3-G point 4.
- Rated current according to HD603/VDE0276-603, Part 3-G, Table 14 when installed underground (buried at ground temperature +20℃ according to HD603/VDE0276-603, Part 3-G, point 5); when used outdoors, according to Table 15 (Installed at +30℃ according to HD603/VDE0276-603, Part 3-G, point 5) . However, when using in or on buildings, please correct with the reduction factor in catalog appendix T12 as necessary.
■Compliance standards/certification
HD603/VDE0276-603.
■Configuration
・Aluminum conductor.
- Abbreviation "re", "se": r = circular conductor shape; s = fan-shaped conductor shape; e = single core; m = stranded wire.
・Insulator: PVC base.
- Compound is contained between the insulator and outer sheath.
・Outer sheath: PVC base.
This is the version of our website addressed to speakers of English in
the United States.
If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.